TMV3 Scheme + DO8 approved (NHS model engineering specification)
Features
| • |
Complete with strainers and check valves. |
| • |
Available in 15mm & 22mm. |
| • |
Provides safe temperature warm water at taps etc. |
| • |
Tip: We recommend that you try to get as equal as possible water pressure on both the incoming hot and cold water supplies. |
| |
|
Working Parameters & Specifications
For both 15mm & 22mm valves.
| • |
Factory temperature setting: |
|
38°C |
| • |
Temperature setting range: |
|
35 - 46°C |
| • |
Temperature, hot supply: |
|
52 - 65°C |
| • |
Temperature, cold supply: |
|
5 - 20°C |
| • |
Minimum hot to mix differential temperature: |
|
10°C |
| • |
Temperature stability: |
|
+ 2°C |
| • |
Maximum pressure loss ratio: |
|
10:1 |
| • |
Working pressure, static: |
|
10 bar mix |
| • |
Maximum hot inlet temperature: |
|
90°C |
|
|
  |
| |
|
|
Approved Specifications
| Code |
Operating pressure |
|
Application |
| HP-S |
High pressure |
|
Shower - max temp 41°C |
| HP-W |
High pressure |
|
Washbasin - max temp 41°C |
| HP-B |
High pressure |
|
Bidet - max temp 38°C |
| LP-S |
High pressure |
|
Shower - max temp 41°C |
| LP-W |
Low pressure |
|
Washbasin - max temp 41°C |
| LP-B |
Low pressure |
|
Bidet - max temp 38°C |
|
|
|
|
High pressure 1 - 5 BAR
Low pressure 0.2 - 1 BAR
| Code |
Operating pressure |
|
Application |
| HP-T44 |
High pressure |
|
Bath fill - max temp 44°C |
|
Suitable for water pressure 1 BAR to 5 BAR